Terminating Shields at the Panel Entry

Column: Technical Notes    Time: 2025-04-01

cable screen is not a drain for interference; it is a reflector. Terminated correctly, it keeps the noise inside the cable. Terminated at both ends on an unshielded system, it carries current it was never meant to carry.

Where to connect

For a signal cable, earth the screen at the panel end only, and insulate it at the field end. Connecting both ends creates a loop that picks up the potential difference between two earth points and injects it directly into the signal. The exception is a cable between two panels on the same earth bar, where both ends can be bonded.

How to connect

Use a screen clamp that bonds the screen to the enclosure over 360°, not a pigtail. 20 mm pigtail has enough inductance to make the screen useless above a few megahertz. Bring the screen through the gland and clamp it at the entry point, before the conductors reach the terminals.

Drive cables

Motor cables are different: the screen must be earthed at both ends, because it carries the capacitive current from the drive output. The cable length note explains why, and the analogue noise note covers the symptoms when this is done wrong. The PLC cabinet is wired with separate earth bars for signals and power so both rules can be followed in the same panel.