Fan and HVAC Automatic Control Cabinet
Ventilation plant usually means several fans that must move together: supply against extract, pressure held steady as filters load up, and a fire mode that overrides everything. These cabinets group the drives, the damper outputs and the sensors in one enclosure with a single interface to the building system.
- Fans per cabinet
- 1 – 6
- Drive rating
- 1.5 – 110 kW per fan
- Control
- PID for duct pressure, temperature or CO₂
Overview
Drives are mounted side by side with a common forced-ventilation duct so that heat from one does not shorten the life of its neighbour. Each fan gets a hand-off-auto selector on the door and a manual speed potentiometer for commissioning.
Where the building has a BMS, the panel exposes Modbus RTU / TCP points, or a BACnet gateway can be fitted. Alarm lists, trend pages and the day / night schedule are configured before dispatch.
Build details
- Drives mounted side by side with a common forced-ventilation duct
- Hand-off-auto selector for each fan on the door
- Manual speed potentiometer for commissioning
- Alarm list and trend page pre-built on the HMI
- Fire-mode override terminal pair for the building system
Specifications
| Fans per cabinet | 1 – 6 |
|---|---|
| Drive rating | 1.5 – 110 kW per fan |
| Control | PID for duct pressure, temperature or CO₂ |
| Sequences | Day / night schedule, setback, fire-mode override |
| Damper / valve outputs | 0–10 V or floating control |
| Interface | Modbus RTU / TCP; BACnet gateway on request |
| Enclosure | Floor-standing steel, RAL 7035, IP54 |
| Options | Differential pressure transmitter, filter alarm, VFD bypass |
Specifications vary with the motor list and the site supply. Tell us the load and the environment and we will confirm the build.
Typical applications
- AHU and fresh-air units
- Car park ventilation
- Clean rooms
- Paint booths
- Kitchen extract
- Dust collection