Drive-to-Motor Cable Length and dV/dt Filters

Column: Technical Notes    Time: 2025-08-24

Motor cables are transmission lines. When the drive switches, the pulse travels down the cable, reflects at the motor, and can arrive back at almost twice the DC bus voltage. On a 400 V supply that is a peak near 1100 V — enough to stress the first turns of the motor winding, and enough to break down a cable that was chosen only for current.

Where the length starts to matter

Most drive manufacturers give a table of permitted cable length without a filter, typically 30 to 50 metres for a shielded cable and considerably less for an unshielded one. Those figures assume a standard motor with a winding that meets IEC 60034-25. Where the run is longer, or the motor is older, the practical answers are a load reactor, a dV/dt filter, or a sine filter — in increasing order of cost and of effectiveness.

The cheaper fixes first

Route the motor cable away from control wiring, keep the screen continuous and clamp it at both ends, and avoid mixing motors of very different cable lengths on one drive. Where the drive feeds several motors, the total cable length is what counts, not the longest single run. The shield termination note covers the earthing detail that makes the difference in practice.

If the run cannot be changed — a submersible pump 200 m down a borehole, a fan on a roof — say so at enquiry stage. The VFD control cabinet can be built with the load reactor or filter inside the enclosure, which is far easier than retrofitting it on site with the plant already running.