Analogue Signals That Drift: Screening and Earthing

Column: Technical Notes    Time: 2025-07-29

Loop reading two bar high at shift change is not a sensor fault. It is usually an earth problem, and it usually appears at the same time every day because something else in the plant switches on then.

Where the current goes

4-20 mA loop should have exactly one earth reference. If the transmitter is earthed at the tank and the PLC analogue card is earthed at the panel, the two earths sit at slightly different potentials. The difference drives current through the screen, which adds to or subtracts from the signal. The error is proportional to the earth potential difference, so it wanders with plant load.

The fixes, in order

First, earth the screen at one end only — normally the panel end — and insulate it at the transmitter. Second, use a separate analogue earth bar rather than the panel chassis. Third, separate analogue cables from drive output cables by at least 200 mm, and cross at right angles where they must cross. Fourth, where the transmitter is powered from the loop, check that the supply is isolated per channel and not shared.

For a channel that has been noisy for years, an isolating amplifier costs less than a day of investigation and eliminates the loop's earth dependence entirely. The shield termination note covers the same issue on digital signals, and the PLC and HMI cabinet is wired with analogue and digital earths kept apart from the start.