Retrofitting a VFD onto an Existing Fan Starter
Fitting a drive to a fan that currently runs direct-on-line is one of the cheapest energy projects in a plant. It is also one where the existing installation quietly sets limits that the quotation should acknowledge.
Check the motor first
older motor designed for direct-on-line duty may not have insulation rated for drive output. Winding insulation class F with a drive-rated specification is what to look for; a motor from the 1990s usually is not. If the motor must be changed, the project cost doubles and the payback calculation changes with it. Check the fan curve as well: a fan selected for a fixed speed often has its duty point at the right of the curve, and slowing it down may drop static pressure below what the duct system needs.
Check the cable and the overload
The existing cable may be unshielded and long, which brings the reflected-voltage problem described in the cable length note. The existing thermal overload is a bimetal relay set for direct-on-line current; with a drive, motor protection moves into the drive, and the old relay becomes a switch unless it is retained for bypass duty. Terminal arrangement inside the starter enclosure usually needs rework, and a starter that was a 400 × 500 enclosure often becomes a 600 × 800 drive panel.
What the retrofit looks like
Normally: new VFD control cabinet with the drive, an isolator, the EMC filter and the control interface to the existing BMS or thermostat; existing motor kept if its insulation allows; existing cable reused if the run is short and the screen can be terminated properly. The cooling note covers the extra heat a drive adds to a plant room that was sized for a starter.