Heat Load in a Drive Panel and When to Add a Fan
Every drive loses between 2 % and 4 % of its rating as heat, and that heat stays inside the enclosure until something removes it. On a 90 kW drive at 3 % loss, that is 2.7 kW of heating inside a steel box — more than a small room heater.
The calculation is short
Add the losses of the drive, the input filter, the transformer if it is inside, and any other heat source. Compare the total with what the enclosure surface can dissipate: for a painted steel enclosure in still air, roughly 5.5 W per square metre per kelvin of temperature difference. 800 × 1000 × 300 floor-standing cabinet has about 3.5 m² of surface, so a 15 K rise above ambient removes around 290 W. Anything more needs help.
The options in order of cost
First, use a larger enclosure — more surface costs less than a cooling unit. Second, add a filter fan with an outlet filter; it is cheap, needs clean air, and is unsuitable in dusty or wet rooms. Third, fit an air-to-air heat exchanger for sealed panels: it moves heat without moving air between inside and outside. Fourth, an air conditioner, which is the only option that brings the internal temperature below ambient and the most expensive to run.
Set the fan or the conditioner to switch on a thermistor inside the panel, not to run permanently. In a cold plant, a permanently running filter fan drags in damp air and creates condensation on cold components. For high-power drives, the VFD control cabinet is often split so the drive sits in its own ventilated section and the control gear in a sealed one. The enclosure thermal note covers the same maths for panels without drives.