Metering and Power Quality Monitoring Options
Metering is bought for two different reasons: billing and diagnosis. They need different instruments, and confusing them produces a board that measures everything badly or nothing usefully.
For billing
class 1 or class 0.5S kWh meter, a CT ratio matched to the load, and a sealable cover. The meter must be readable without opening the board, so a door-mounted display or a window. Where the utility supplies its own meter, the panel provides the CTs, the fuse protection on the voltage circuit and a mounting space.
For diagnosis
Power quality matters more than energy: harmonics, unbalance, sag and swell. class A analyser costs several times a kWh meter and answers questions a kWh meter cannot. On a board feeding drives, harmonic distortion of 30 % or more is common and shows up as failed capacitors and hot neutrals rather than as an energy problem.
The middle ground
Multifunction meters with Modbus output give voltage, current, power, power factor and THD per phase for a modest cost, and log to a PLC or a gateway. That covers most industrial requirements. The power factor note explains what to do with the readings, and the power distribution cabinet is quoted with metering as a defined option rather than a last-minute addition to the door.