Power Factor Correction in a Distribution Panel
Capacitor banks fail early for one reason: harmonics. bank installed on a supply with 30 % voltage distortion draws a disproportionate current at the harmonic frequencies, overheats, and swells within a year.
Detuned reactors are not optional on drive-heavy supplies
detuned reactor shifts the bank's resonance below the lowest harmonic present, typically to 189 Hz for a 50 Hz supply, which protects the capacitors from the fifth and seventh harmonics. Without it, the bank and the supply inductance form a resonant circuit that amplifies exactly the harmonics the drives produce.
Steps, not one big bank
Switching in a single large bank produces a voltage step every time it connects. Stepped banks of 10 to 25 kvar with a controller that follows the load give smooth correction and avoid hunting. The controller needs a target power factor — 0.95 is normal, 1.0 causes over-correction at light load and is a common cause of leading power factor penalties.
Where the bank sits
Central compensation at the main board is cheapest per kvar. Local compensation at a large motor is more precise but risks self-excitation if the motor is driven by a drive or can overrun. The metering note explains how to measure the need, and the power distribution cabinet can include the bank, reactor and controller as a tested assembly.