Choosing the Incoming Breaker for a Distribution Board
The incoming breaker sets three things at once: the price of the board, the fault level it can survive, and whether the utility will accept it. Getting it wrong at quotation stage is expensive, because frame sizes do not shrink later.
Three figures decide it
Full load current of the installation, prospective short-circuit current at the board terminals, and the discrimination requirement with the upstream device. The first sizes the frame, the second sizes the breaking capacity, the third decides whether the trip unit must be adjustable. Only the first is usually stated in an enquiry; the other two are what the panel builder has to ask for.
Breaking capacity is not negotiable
36 kA breaker in a board that will see 50 kA is not a marginal choice, it is a fault waiting for a reason. Where the actual fault level is unknown, the utility can usually provide it, and a conservative assumption of 25 kA at a small industrial supply is common in Europe and China. In a plant fed by its own transformer, calculate it from the transformer impedance.
Adjustable trip when selectivity matters
Where the board feeds sub-boards and a single fault should not take out the whole installation, an adjustable thermal and magnetic trip is needed, along with time-current curves to prove the discrimination. The selectivity note covers the calculation, and the power distribution cabinet is quoted with the fault level written into the specification so the breaker is not chosen by habit.