Column: Technical Notes    Time: 2025-04-04

Cable duct rated at 60 % fill becomes a heater when every slot is used. The rating assumes the wires can dissipate heat; at 80 % fill they cannot, and the temperature inside the duct rises well above the panel ambient.

The real fill

Count the cross-section of every conductor in a section of duct, not just the visible bundle. Control wiring fills faster than expected — 1.5 mm² wires in a 40 × 60 mm duct reach 60 % at around 90 conductors. Leave 40 % free and the duct stays cool and the wiring can still be traced.

Heat sources

Duct near drives, transformers or heating elements carries heat from outside as well as from its own conductors. Where a duct must pass close to a heat source, use a barrier or route it around. Vertical ducts between hot and cool zones create a chimney effect that pulls dust through the panel.

Layout consequence

Generous duct costs a little more steel and slightly more enclosure volume, and it is the first thing cut when a panel is being value-engineered. The saving is recovered as a temperature problem two years later. The thermal note covers the panel-level calculation, and the custom control panel is laid out with duct sized to the final wiring count rather than the first draft.