Thermal Rise in a Sealed Enclosure
sealed enclosure has no cooling. Heat generated inside raises the internal temperature until the enclosure surface can dissipate it, and if that balance point is above the rating of the components, the panel fails slowly rather than dramatically.
The surface calculation
Effective surface area × heat transfer coefficient × temperature difference = heat removed. For painted steel in still air, the coefficient is around 5.5 W/m²K; for stainless it is slightly lower. 600 × 800 × 300 wall-mounted enclosure has about 1.7 m² effective area, which removes roughly 140 W at a 15 K rise.
What is inside
Contactors, relays and breakers produce little. Drives, transformers, power supplies and heating elements produce a lot. Add them up from the datasheets — a 24 V 10 A supply loses 20 to 30 W, a 2 kVA control transformer loses 60 to 80 W, and a small drive can lose several hundred. The total is usually higher than the first estimate.
Choosing the answer
Below the surface limit, nothing is needed. Above it, a filter fan with an outlet filter is cheapest but admits dust. air-to-air heat exchanger keeps the IP rating and handles moderate loads. cooling unit is the only option when the internal temperature must fall below ambient. The drive heat load note works the same calculation for drive panels, and the custom control panel is quoted with the thermal calculation attached.