Pressure Control for Pump Sets: A PID Setup That Holds
Pressure control is the most common closed loop on a pump panel and the one most often left hunting. The drive is doing what it was told; the settings and the sensor tell it to do the wrong thing at the wrong speed.
Start with the sensor
0-10 bar transmitter on a 6 bar system gives 1.67 V per bar, which is coarse. 4-20 mA transmitter with the same range gives far better resolution and is immune to the voltage drop on a long cable. Fit the tapping on the discharge header, at least five pipe diameters downstream of the pump and away from the non-return valve where pressure pulses form.
Settings that stop the hunting
Set the proportional gain low and the integral time long at first, then reduce the integral time until the loop responds in roughly the time the system needs to change pressure. Add a feedback filter of 1 to 2 seconds — long enough to ignore pump pulses, short enough not to destabilise the loop. Set a minimum speed of 25 to 30 Hz so the pump does not run at a speed where it cannot build head, and a sleep function so the drive stops when demand disappears rather than running at minimum speed all night.
The mechanical side
No drive setting fixes a system with no accumulator and a tap that opens instantly. On small networks, a pressure vessel of a few litres smooths the loop more than any parameter change. For sets with several pumps, the duty and standby changeover note covers the logic above the drive. Ask for the VFD control cabinet with the duty point and pipe size, and the settings are made before dispatch.