Line Reactors, DC Chokes and Harmonic Limits
Reactors are quoted on almost every drive panel and rarely specified. Buyers ask for "a reactor" without saying whether they mean a line reactor on the input, a DC choke in the drive's intermediate circuit, or a load reactor at the motor terminals. The three do different jobs and are not interchangeable.
Line reactor on the input
Fitted between the supply and the drive, it reduces the harmonic current drawn from the network and softens the voltage notching that a drive imposes on a shared busbar. Standard impedance is 2 % or 4 %, with 4 % the usual choice where several drives share a supply or where a generator is involved. It does not make a drive "harmonic free" — it typically takes total current distortion from around 40 % to the low thirties.
DC choke and load reactor
DC chokes are built into many drives above 7.5 kW and do a similar job inside the drive. Where the enclosure is shared, they are the cheaper way to reach the same result and need no panel space. Load reactors belong at the motor end, fitted when the cable run is long enough to cause reflected voltage at the motor — the limits are in the cable length note.
Where 5 % is still not enough
On a weak supply with a high source impedance, or where the utility enforces IEEE 519 at the point of common coupling, passive reactors are only the first step. tuned filter or an active front end may be required. Tell us the short-circuit level at the panel and the distortion limit you must meet, and the VFD control cabinet is designed around it rather than around a catalogue line.