Earth Leakage and RCD Choice on Drive Circuits

Column: Technical Notes    Time: 2025-08-10

Drives leak current to earth by design. The EMC filter capacitors connect each phase to the protective earth, and the switching output adds capacitive current through the motor cable. On a 30 kW drive this can reach several hundred milliamps at the switching frequency — far above the 30 mA that a standard residual current device is set to detect.

Why the RCD trips

Common domestic and commercial RCDs are Type AC, which respond only to sinusoidal alternating residual current. drive produces residual current with a high-frequency component and, in single-phase units, a DC component that can blind a Type AC device entirely. Fitting one on a drive circuit produces either nuisance tripping or, worse, no protection at all.

What to use instead

Type B devices respond to DC, AC and high-frequency residual current and are the correct choice for drive circuits where earth leakage protection is required. Sensitivity is normally 300 mA rather than 30 mA, because the drive's own leakage sits above the lower threshold. Where 30 mA protection is mandatory — socket outlets, some wet areas — the drive circuit should be separated from those circuits rather than protected by a device it will trip.

Earthing quality decides much of this. high-impedance earth path raises the voltage on the enclosure and increases leakage elsewhere. The shield termination note covers the motor cable screen, and the VFD control cabinet is supplied with a separate earth bar for drives and filters so the leakage path is deliberate rather than accidental. Where the supply is TT, check the neutral and earth bar note.

More News

WhatsApp +852 6174 0278WhatsApp +852 6177 3422