Roots Blowers: Starting Load and Protection
Roots blowers are positive displacement machines: the load torque is roughly constant and the starting current is high for longer than a fan's. Treating one like a centrifugal fan is a reliable way to trip the supply.
Starting method
Direct-on-line start of a 45 kW blower draws five to six times rated current for several seconds and produces a pressure pulse through the pipework. Star-delta reduces the current but not the pulse. soft starter or a drive is the usual answer; a drive also allows the speed to follow process demand and often pays for itself in energy.
The bypass valve
Start against an open bypass so the blower does not build pressure before it is up to speed. Close the bypass slowly after the motor is at full speed. If the valve is operated automatically, the panel must sequence it: open before start, close after a delay, and open again on stop.
Protection
Overload set to the motor's service factor rather than to nameplate current, plus a temperature sensor on the bearing housing and, where the process allows, a pressure switch on the discharge. Positive displacement machines do not forgive a blocked discharge. The interlock note covers the sequencing, and the vacuum pump control cabinet is built for blower duty with the bypass logic included.