Control for Liquid Ring Vacuum Pumps
Liquid ring pumps are robust and forgiving, which is why they survive in plants where other vacuum technologies fail. Their control panel has one job above all: protect the seal water supply.
Seal water is the critical interlock
Without water the pump runs dry, the ring collapses, and the mechanical seal is destroyed within minutes. flow switch on the seal water line, wired to stop the pump, is the single most important input on the panel. Pressure switches alone are unreliable at low flow rates; a paddle or thermal flow switch is better.
Cavitation and the inlet
Liquid ring pumps cavitate when the inlet pressure falls below the vapour pressure of the liquid being handled. The symptom is noise and vibration, and the cure is either a lower water temperature or a partial air bleed into the inlet. small solenoid bleed valve controlled from the panel solves most cases and costs little.
Starting and stopping
Start with the inlet valve closed and open it after the ring has formed, typically two to three seconds. Stop by closing the inlet first, then stopping the pump, then shutting the water after a short delay. The sequence matters more than the components. The multi-pump interlock note covers sets of two or more, and the vacuum pump control cabinet is built with the sequence and the flow switch included.