Insulation Resistance Testing: Values and Limits
Insulation resistance is the first test that tells you whether a panel is safe to energise. It is also the test most often done on the wrong setting, at the wrong time, on a panel that is not isolated.
What to do
Disconnect electronic devices, drives and surge arresters. Test at 500 V DC between each phase and earth, and between phases, for one minute. Record the reading after the full minute, not immediately — a reading that climbs is a reading that has capacitance in parallel, which is normal in a large panel.
What the numbers mean
One megohm is the minimum for a new low-voltage assembly; ten megohms or more is typical of a clean, dry panel. reading that falls over successive tests indicates moisture, and a reading that is erratic indicates a loose connection rather than insulation failure. Below one megohm, the panel does not ship.
What it does not prove
Insulation resistance says nothing about whether the wiring is correct, whether the phases are in the right order, or whether a terminal is tight. Those are continuity and function tests. The continuity note covers the first, and the custom control panel is delivered with the insulation test results recorded per panel serial number.