Hipot Testing: What It Can Damage
High potential testing is a powerful check on insulation and a reliable way to destroy electronics. 2.5 kV test applied to a panel with a drive still connected will damage the drive's input rectifier, and the failure may not appear until the drive is on site.
What must be disconnected
Drives, soft starters, surge arresters, power supplies, PLC modules, meters and any device with a semiconductor input. That is most of a modern panel. Where disconnection is impractical, the test is done at reduced voltage or not at all, and the decision is recorded.
When hipot is required
Some markets and some customers require a dielectric test on every assembly; others accept insulation resistance alone. Where it is required, do it on the busbar and wiring before the electronics are fitted — a sequence that costs nothing at design stage and is impossible afterwards.
Alternative
Insulation resistance at 500 V DC plus a visual check of clearances catches most of what hipot would find, without the risk. The insulation test note covers the procedure, and the custom control panel is tested to whichever regime the customer's specification requires, stated at order stage.