Dry Run Protection That Does Not Nuisance Trip
Dry running destroys a pump in minutes, and the protection against it is often set so conservatively that it trips during normal operation. Both failures cost money.
Three signals, three weaknesses
Current: a dry-running pump draws less current, but so does a pump at low flow. Flow switch: direct and reliable, but another fitting in the pipe. Temperature: responds slowly, but catches the case where flow is present and cooling is not. Each alone gives false trips or missed events.
Combining two
Current below a threshold for longer than 10 seconds, confirmed by low flow, is a reliable dry-run signal. Use a delay long enough to cover a normal start and short enough to save the seal — 10 to 15 seconds suits most small pumps. Where the pump is a submersible on a long cable, the current signal is less reliable and the flow switch becomes primary.
Reset behaviour
Dry-run trips should latch and require a manual reset. Automatic reset will restart the pump into the same dry condition every few minutes, which is worse than staying stopped. The duty and standby note covers the transfer on failure, and the pump control cabinet can be configured with either protection scheme to the customer's preference.