News
N

News

News

Building a Terminal Schedule Buyers Can Read

Column: Technical Notes    Time: 2025-07-17

Terminal schedules are written for the person standing in front of the panel with a cable and a screwdriver. If they have to call the panel builder to understand it, the document has failed regardless of how complete it is.

What each row needs

Terminal number, device tag, wire number, cross-section, signal type and a short description. Six columns, no more. Signal type is the one most often left out and the one that saves the most time: DI, DO, AI, AO, 24 V, 0 V, PE. With that column, an electrician knows at a glance which terminals can be tested with a multimeter and which must not be.

Grouping

Group terminals by function, not by device: all digital inputs together, all analogue inputs together, all 24 V distribution together. Inside each group, follow the field cable numbering, not the PLC address, because the field cable is what arrives on site. Reserve terminals belong at the end of each group, clearly marked.

Format

A3 printed and folded in the door pocket, plus a PDF. Landscape, one group per block, terminal numbers in bold. The cable schedule note covers the field side of the same information, and the PLC and HMI cabinet is delivered with the printed schedule in the door and the editable file on request.