Designing the 24 V DC Supply and Its Protection
The 24 V DC supply is the part of a control cabinet most likely to cause a whole-panel shutdown and least likely to be designed. One power supply feeding PLC, relays, indicators, sensors and door lamps is common and is a single point of failure for everything.
Load budget before selection
Count the load in three groups: continuous (PLC, sensors, transmitters), intermittent (relays, solenoids, contactor coils) and occasional (door lamp, test points). Add the continuous load, add 30 % of the intermittent load, and size the supply at 1.3 times the total. Contactor coils draw a surge several times their holding current, so a supply sized on holding current alone browns out every time a contactor pulls in.
Protection and distribution
Each outgoing circuit should have its own fuse or electronic breaker, sized to the cable, so a shorted sensor does not take down the PLC. Group the 24 V distribution on its own terminals with a clear schedule. Where the process cannot stop, use two supplies with a redundancy module — not two supplies wired in parallel, which is a way to damage both.
The details that fail
Terminals tightened on stranded cable without ferrules, supplies mounted at the bottom of the panel where heat collects, and no spare capacity left for the four sensors added in year two. The ferrule note covers the first, and the PLC and HMI cabinet is normally built with the 24 V distribution on a dedicated rail and a 30 % margin on the supply.