Moisture Barriers for Sea Freight

Column: Company News    Time: 2025-02-09

Condensation inside a container ruins more panels than rain ever does. steel enclosure that crosses the equator passes through temperature swings of 30 K, and moisture condenses on every cold surface inside the case.

Three layers

First, the panel itself: door gaskets closed, glands plugged, and a desiccant bag inside the enclosure for long voyages. Second, the case: a VCI (vapour corrosion inhibitor) film bag around the panel, sealed, with the air squeezed out. Third, the container: no wet cargo nearby and, where possible, a desiccant blanket.

What not to do

Shrink wrap directly on a painted panel traps moisture against the paint and produces blistering that looks like a coating failure. Sealed plastic with no desiccant creates a humid microclimate. Both are common and both are worse than no wrapping at all.

On arrival

Open the case in a dry space if possible, remove the VCI film within 24 hours, and check for condensation on the inside of the door. Photograph before wiping. The case note covers the outer packaging, and the custom control panel sea freight packing includes VCI film and desiccant as standard.