Expansion is decided at design stage, when it costs nothing, or during a shutdown, when it costs everything. The three things that matter are spare ways, spare height and a cable route.

Spare ways

Twenty per cent spare outgoing ways is normal for a plant board, with the spare ways fitted with blanking plates and the busbar extended. board that is full at commissioning guarantees a second board within three years.

Spare height and space

Leave one full 300 mm section empty, with the busbar continuing through it and the cable duct carried across. That space takes a feeder later without cutting steel. Reserve space at the bottom for cable entry: a board with no spare gland plate cannot accept a new feeder without drilling a painted enclosure.

Cable route and documentation

Show the intended expansion on the drawing, including the direction the new cables will arrive. The next electrician will use the drawing, and a drawing that has no room for growth is read as full. The form separation note explains how barriers affect spare space, and the power distribution cabinet can be specified with the expansion allowance built in from the start.