News
N

News

News

Cable Sizing for Distribution Cabinets

Column: Technical Notes    Time: 2025-06-22

Cable sizing looks like a table lookup and is really an argument between four tables that rarely agree: current capacity, derating for ambient, derating for grouping, and voltage drop.

Start with the installation method

Clipped direct, in conduit, on a tray, in free air — each gives a different base current for the same conductor. 16 mm² copper cable carries about 100 A clipped direct and around 70 A in a thermally insulated wall. Picking the wrong row is the most common sizing error, and it is invisible once the cable is in.

Then derate

Ambient above 30 °C, more than one circuit in the same tray, and any enclosure all reduce capacity. In a plant room at 45 °C, a factor near 0.87 applies before grouping. Two trays of cables together can take another 20 % off. The result is often two sizes larger than the first guess.

Voltage drop last

Drop is a limit as well as a nuisance: 5 % at the terminals for power circuits, 3 % for lighting is the usual convention, and a long feeder to a motor can exceed both while the current capacity is fine. The neutral and earth bar note covers the return path, and the power distribution cabinet is quoted with terminal sizes that match the cable schedule rather than a generic rating.

More News

WhatsApp +852 6174 0278WhatsApp +852 6177 3422