Busbar Supports, Spacing and Short-Circuit Withstand

Column: Technical Notes    Time: 2025-07-04

Busbar size gets all the attention; support spacing decides whether the bar stays where it was put. Under fault current, the electromagnetic force between two bars can reach several tonnes per metre, and a bar on supports 400 mm apart will bend where one on 250 mm supports will not.

The force is proportional to current squared

Doubling the fault current quadruples the force. At 50 kA peak, a typical 100 × 10 mm copper bar pair needs supports every 300 mm or so to stay within the permissible stress. At 25 kA the same bar can be supported at 500 mm. The manufacturer's table gives the figures; the mistake is to use the table for the wrong current.

Clearance as well as support

Phase-to-phase and phase-to-earth clearance must hold under the same fault, and the clearance depends on the pollution degree of the installation. In a dusty plant, the required clearance increases because dust bridges the gap. Insulating supports with barriers between phases solve both the mechanical and the clearance problem in one component.

What to ask for

short-circuit withstand figure with a duration — 50 kA for 1 s is a different design from 50 kA for 0.1 s. The form separation note explains how barriers change the layout, and the power distribution cabinet is built to the declared fault level rather than to a standard assumption.