News
N

News

News

Variable Speed on HVAC Supply and Return Fans

Column: Technical Notes    Time: 2025-05-29

Fan energy scales with the cube of speed. Halving the speed of a supply fan cuts its power to about an eighth, which is why a drive on an HVAC fan is one of the few energy measures with a payback under two years.

What to control

Static pressure is the usual control variable: a pressure transmitter in the main duct, setpoint at the design pressure, drive speed trimmed to hold it. Where the system has variable dampers, pressure control lets the dampers open and the fan slow, and that is where the savings are. Duct temperature control is an alternative for systems where flow matters more than pressure, but it responds slowly and needs more filtering.

Minimum speed and safeties

Set a minimum speed of 40 to 50 % so the fan does not stall and the motor stays cooled, and a maximum of 100 % as a hard limit. Add a duct pressure high-limit switch that stops the fan, and a fireman's override input that forces full speed regardless of the control signal. The override must be hard-wired, not software only.

Retrofit considerations

existing fan motor may not be drive-rated, and the belt drive may not tolerate the lower speeds without slipping. The fan retrofit note covers the motor check, and the fan and HVAC control cabinet is quoted with the pressure transmitter and the fire override included rather than as extras.