Fire Mode and Smoke Control in Fan Panels

Column: Technical Notes    Time: 2025-05-27

Fire mode is a single input that changes how a fan panel behaves, and it is the requirement most often implemented in software when it should be in hardware.

What it must override

Normal control, time schedules, damper interlocks that would otherwise stop the fan, and any VFD control signal. In fire mode, the fan runs at full speed and the damper opens, whatever the BMS is asking for. The override must be a hard-wired signal into the drive or contactor circuit, so it works when the controller is dead.

What it must not override

The motor protection. fan that burns out in a fire is no better than a fan that is stopped, and the protection is also what prevents a fire from starting in the panel. Thermal overload stays in circuit; only the control logic is overridden.

Testing at handover

Prove the override with the BMS disconnected, and record the result. Then prove that the fan restarts normally when the signal is removed. panel that goes into fire mode and cannot come out is a panel that will be bypassed by maintenance within a month. The HVAC drive note covers the control side and the fan and HVAC control cabinet is built with the fire input on a dedicated terminal block and labelled.