News
N

News

News

Damper Actuators and Feedback Wiring

Column: Technical Notes    Time: 2025-05-24

Damper actuators are simple devices that fail in predictable ways, and almost every failure is a wiring detail rather than a mechanical one.

Spring return and fail position

Spring return actuators drive the damper to a defined position on power loss. On a supply fan, the damper should close on power failure so the fan does not freewheel and pull air through a stopped system. On an exhaust fan it may need to open. Decide the fail position from the process, not from what is on the shelf, and write it on the drawing.

Feedback and end switches

The 0-10 V feedback from a modulating actuator is not always proportional near the ends — most units compress the first and last 5 %. End switches give a discrete confirmation of fully open or fully closed and should be used for interlocks, with the analogue signal used only for indication. Two-wire control with a shared 0 V is not acceptable for long runs; use a four-wire connection.

Commissioning

Set the mechanical stroke limits with the damper connected, not on the bench. Check the closed position against the seal, and record the open and closed feedback voltages on the panel label. The fire mode note covers the override, and the fan and HVAC control cabinet is wired with damper power on a protected circuit separate from the control supply.

More News

WhatsApp +852 6174 0278WhatsApp +852 6177 3422