What an IP Test Actually Verifies
IP65 on a datasheet means a sample passed a test in a laboratory. It does not mean the installed panel will keep dust out for ten years, because the test is done once, on a new gasket, in a defined configuration.
What the test does
First digit: solids. 5 means dust protected — not dust tight, some dust may enter but not enough to interfere. 6 means dust tight. Second digit: water. 5 is jets from any direction, 6 is powerful jets, 7 is temporary immersion, 8 is continuous immersion. Each is tested for a stated duration and flow, on a complete enclosure with the specified glands.
What changes after installation
Door gaskets compress and take a set. Cable glands are added by site electricians with the wrong size. cut-out is drilled for an extra meter and not sealed. Any of these voids the rating, and the panel that was IP65 in the workshop is IP44 on site within a year.
Specifying sensibly
IP54 indoors, IP65 for washdown, IP66 or IP67 for outdoor exposed. Going higher than needed costs money and traps heat, which shortens component life. The gland plate note covers the most common leak path, and the custom control panel is supplied with the IP rating stated and the gland configuration that maintains it.