Gland Plates, Blind Entries and Spare Capacity
Cable entries are the part of an enclosure that is decided last and costs most to change. gland plate drilled for six cables cannot accept a seventh without a new plate, and a new plate means a new hole in a painted enclosure.
How many spare entries
Twenty per cent spare capacity in the gland plate, with blanking plugs fitted, is normal for a process panel. Where the plant is likely to expand, a removable plate covering a third of the base is better: it can be replaced entirely rather than drilled. On smaller wall-mounted enclosures, a single 200 × 200 mm plate is usually enough.
Blind entries and sealing
blind entry is a plate with no holes, sealed with a gasket and four screws. It keeps the IP rating until the first cable arrives, and it costs a fraction of a gland. Where the enclosure is outdoors, the plate must be at the bottom and the glands must face down, with a drip loop in the cable.
Gland selection
Match the gland to the cable diameter, not to the hole. gland that is too large compresses the seal unevenly; too small and it will not grip. For armoured cable, the gland must bond the armour to the enclosure earth. The door stiffener note covers the sealing on the door side, and the custom control panel is quoted with gland plates sized to the cable schedule.