Door Stiffeners and Gasket Compression
gasket only seals if the door presses evenly on it. On a 600 mm wide door, the middle bows outward under its own weight and under the pressure of the hinges, and the gasket at mid-height loses compression even though the corners are tight.
When stiffening is needed
As a rule, doors wider than 600 mm or taller than 1200 mm need a stiffener — a folded profile welded or bonded across the door, or a return flange deep enough to resist deflection. Below that size, a 25 mm return is usually sufficient. The test is simple: close the door on a strip of paper at five points and pull. If the paper slides out at the middle, the door needs stiffening.
Where the stiffener goes
Horizontal across the middle for a wide door, vertical for a tall narrow one, and always on the inside so it does not collect water. stiffener welded after painting distorts the paint on the outside face; it belongs before the coating line, which means the door design has to be decided before the sheet is cut.
Hinges and latches
Stiffening does not compensate for too few latches. Two latches on a 1200 mm door leave the middle unsupported no matter how rigid the panel. Three-point latching is standard above 1000 mm. The gland plate note covers the other half of the sealing problem, and the custom control panel is built with door stiffening matched to the enclosure size.