Dust-Proof Panels for a Quarry Conveyor Line
Quarry conveyor line, fine limestone dust everywhere, and a control room 300 metres from the drives. The previous panels failed through dust ingress rather than component failure.
Dust is conductive
Limestone dust is alkaline and mildly conductive when damp. Inside a panel it bridges clearances, blocks filter fans and settles on heat sinks. The first symptom is usually a nuisance earth fault, and the second is a failed drive.
Build response
Sealed enclosures with positive pressurisation from a filtered air supply, at a pressure of about 30 Pa so air leaves the panel rather than entering. Door gaskets in silicone, and all cut-outs sealed. Filter mats serviced on a schedule rather than on failure, with a differential pressure gauge on the door so the maintenance team can see when they are blocked.
Layout
Drives in a separate section with their own filtered ventilation, control gear in a sealed section. Cable entries from below through a sealed gland plate, with the panel mounted on a 300 mm plinth so dust does not collect at the cable entry. The IP test note explains what the rating does and does not guarantee, and the custom control panel for dusty plants follows this arrangement.