Cold Store Panels at Minus 25 °C

Column: Company News    Time: 2024-12-24

Cold store at minus 25 °C, with the control panel inside the store because the client wanted the operator to work next to the process. Standard components do not behave at that temperature.

What stops working

Standard contactors become sluggish as lubricant thickens, and below about minus 20 °C some will not latch reliably. Standard PVC cable becomes brittle. LCD displays lose contrast and response. Batteries in HMIs fail.

Specification

Low-temperature contactors rated to minus 40 °C, silicone-insulated cable, a heated enclosure with a thermostat holding the internal temperature at minus 5 °C, and an HMI rated for the range or mounted outside the store. Door gaskets in silicone so they do not harden.

The heater detail

The heater must be on a circuit independent of the process supply, so a shutdown does not leave the panel at minus 25 °C overnight with condensation forming when it restarts. 200 W heater on a thermostat is enough for a 600 × 800 enclosure. The thermal note covers the calculation in reverse, and the PLC and HMI cabinet is available in a low-temperature configuration.