Brewery Cellar Control in a Wet Environment

Column: Company News    Time: 2024-12-26

Brewery cellar at 4 °C, hosed down nightly, with a cleaning cycle that sprays caustic at 80 °C. The panels sit in the cellar because the cable runs are short and the process is controlled from there.

Environment

Two problems at once: condensation on cold components when the cellar door opens to a warm corridor, and chemical attack on gaskets and labels during cleaning. Standard painted steel and printed labels both fail within two years.

Response

304 stainless enclosures, silicone gaskets, and engraved labels. Anti-condensation heaters on a humidistat rather than a thermostat, because the problem is humidity rather than low temperature. All glands entering from below with drip loops, and the panel door fitted with a rain shield above it to deflect the hose.

Control

Fermentation temperature control through jacket valves, with a manual override keyed to the cellar master. Cleaning-in-place sequences were left on the existing dedicated controller rather than moved into the PLC, because a change to a CIP recipe should not require a program download. The food plant case covers the washdown specification, and the PLC and HMI cabinet is built to the same standard.