Busbar and Short-Circuit Ratings in Distribution Boards

Column: Technical Notes    Time: 2026-06-11

Distribution boards are bought on one number: the current rating. The number that decides whether the board survives a fault is a different one, and it is usually missing from the enquiry.

Two currents, not one

Continuous current (In) is what the board carries all day. Short-time withstand current (Icw) is what it survives for one second during a fault, and peak withstand (Ipk) is the first-cycle electromagnetic force that tries to bend the bars apart. Confusing the three is how a 630 A board ends up as scrap after a downstream fault.

  • In — 250 A, 400 A, 630 A, 1250 A. Thermal limit, set by bar cross-section and ventilation.
  • Icw — 15 kA, 25 kA, 50 kA for 1 s. Thermal limit under fault, set by mass and by how fast the protection clears.
  • Ipk — roughly 2.1 times Icw for a 50 Hz system. Mechanical limit, set by support spacing.

Send the prospective short-circuit current at the board terminals and the two ratings can be matched. Without it, we quote a default and mark the assumption on the drawing.

The ampacity table is not the rating

Copper bar tables give a current for a bar in free air at a stated temperature rise, usually 65 K over 35 °C ambient. Inside a closed enclosure, with a cable loom in front of the bars restricting convection, the same bar runs hotter. Practical figures for a painted steel enclosure, 40 °C ambient, 70 K rise:

Bar (copper)Free airIn enclosure
20 × 5 mm260 A200 A
30 × 5 mm365 A280 A
40 × 5 mm470 A360 A
50 × 10 mm1000 A780 A

Derating is why two boards of the same nominal rating can be built very differently. Ask for the enclosure ambient and whether the board is wall-mounted or floor-standing with ventilation.

Support spacing and the peak

Electromagnetic force between parallel bars under fault is proportional to the square of the current and inversely proportional to the gap. At 25 kA peak the bars of a 630 A board can see several hundred newtons per metre, enough to bend an unsupported run and to close the gap between phases.

Insulators every 300 to 400 mm on the main run, and a support either side of every tee or reduction. It is the least visible part of a board and the first thing that fails when it is missing.

Coordination with the breaker

The board's withstand rating is only meaningful against the protection upstream of it. Where the incoming breaker clears a fault in 20 ms, the bars see a fraction of the one-second energy; where the protection is a slow fuse or a breaker with a long delay, they see much more. Cascade data from the breaker manufacturer covers this, and it is worth reading before downsizing a bar to save cost.

Two practical rules we apply:

  • Choose the bar for the continuous current with the enclosure derating applied, then check the withstand against the real clearing time.
  • Never let a cable lug bolt directly to a bar run without a support within 100 mm. The lug's weight and the bending moment from the cable are a fatigue point.

What to put in the enquiry

Board rating, prospective fault current, supply arrangement, ambient, cable or busbar outgoing, and whether the board is a main or a sub-board. Six lines. With those, the power distribution cabinet is specified once and does not come back for a rebuild after the first fault study.