News
N

News

News

One Hundred PLC Panels for a Water Treatment Upgrade

Column: Company News    Time: 2026-03-03

Framework order for one hundred PLC panels closed this month with the eighth and final batch. The panels serve a water treatment upgrade built in stages, with each stage energised before the next was installed.

What the site needed

Treatment works upgrade split across filtration, dosing and pumping areas. Each area had its own MCC and its own PLC, reporting to a plant SCADA over Ethernet. The electrical package had to follow the civil programme: no storage for panels, no ability to install a batch early, and no tolerance for a panel that did not match the previous one.

Requirements that shaped the build:

  • Identical terminal layout across all one hundred panels, so commissioning staff could move between areas without re-reading drawings.
  • IP65 enclosures, 304 stainless in the dosing areas where chemical mist settles.
  • Anti-condensation heaters on all outdoor kiosk panels, on a thermostat.
  • Test sheets issued per panel, with the panel serial number on every page.
  • Spare parts for the whole framework held as one kit, not per batch.

How it was split

Eight batches over five months, sized to the civil contractor's programme rather than to our production convenience. Batch sizes ranged from six to twenty-two panels, which is inefficient in the workshop and correct for the site.

BatchPanelsAreaEnclosure
16Intake pumpingIP65 painted steel
2 – 328FiltrationIP65 painted steel
411Chemical dosingIP65 304 stainless
5 – 630Distribution and MCCIP54 floor-standing
714Sludge handlingIP65 painted steel
811Outdoor kiosksIP55 with heater

Where the savings came from

Building one hundred panels that differ only in software and motor size is a production exercise, not an engineering one. Three decisions did the work:

  • One drawing set. Numbering, terminal positions, label positions and device designators fixed at batch one and never renumbered. Changed component positions were accommodated inside the existing designators.
  • Standard sub-assemblies. PLC sub-panel, 24 V distribution, surge protection and interface relays built as identical modules on a jig, then fitted.
  • Batch testing on one rig. The jig brought the field terminals out to a patch panel, so function testing was the same physical routine for every panel.

The result was a first-pass test success rate above 97 per cent across the framework, with the remaining items mostly labelling and torque checks rather than wiring faults.

What went wrong

Batch four, the stainless dosing panels. Chemical mist in a dosing room is one thing; the client's process engineer specified 316 for two of the eleven after a chloride survey came back higher than the original estimate. Those two were re-cut and re-shelled, which cost three weeks on that batch.

Lesson we now apply earlier: ask for the chloride exposure figure, not the room name. Dosing room can mean anything from lime slurry to sodium hypochlorite, and the material answer differs.

Handover

Final batch shipped with the consolidated as-built set: one drawing book, one test sheet per panel, component list and the spare parts kit. Commissioning ran area by area behind the civil programme and closed with no panel-related delay recorded — which for a hundred panels is the number we care about.

More News