VFD Cables, Shielding and Earthing in Practice

Column: Technical Notes    Time: 2025-10-28

Most drive-related noise problems are cable and earth problems. The drive is blamed, replaced, and the problem follows the new drive — because the installation did not change.

What leaves a drive on the motor cable

Drive switches its output at a few kHz with rise times in the hundreds of nanoseconds. The cable to the motor is not a wire; at those frequencies it is a transmission line, and it radiates. Two effects follow:

  • Common-mode current on the motor cable's screen and on the protective earth, flowing back to the drive through any path it can find — including instrumentation cable screens, building steel and the panel's own earth bar.
  • Bearing current in the motor, from the same common-mode voltage dividing across the shaft.

What to specify between panel and motor

CableWhere it is rightNote
Unshielded 4-coreShort runs in a metal conduitConduit must be earthed both ends
Shielded, symmetrical 3-core + PEStandard drive cableScreen bonded 360° both ends
Armoured with overall shieldMechanical protection neededArmour is not an EMC screen unless bonded
Dedicated VFD cableLong runs, sensitive areasThicker insulation, low capacitance

Three conductors plus a symmetric earth, rather than four equal cores, keeps the magnetic field balanced and reduces the current that has to return through the screen.

Terminating the screen properly

The screen has to be bonded to the enclosure at both ends, at the point of entry, with 360-degree contact. This is the single detail most often done wrong.

  • Use an EMC gland or a screened clamp on a bare metal bar, with the screen folded back over the gland cone.
  • Strip the outer sheath only as far as the clamp; keep the screen continuous up to the enclosure wall.
  • Do not twist the screen into a pigtail and land it on a terminal. Pigtail provides a low-frequency path and almost nothing above a few MHz, which is exactly the range a drive generates.
  • Bond at the motor end too, in the motor terminal box, with the same 360-degree clamp.

Where a screen is bonded at one end only — a habit borrowed from low-frequency signal practice — the cable behaves as an antenna.

The earth bar in the panel

Noise returning through the protective earth is the mechanism that couples drives into everything else. Three arrangements make a difference:

  • Separate EMC bar for screens, bolted to the enclosure with paint removed at the contact faces, distinct from the PE terminal rail.
  • Short, wide connections. Braid rather than round wire, as short as the layout allows. Inductance, not resistance, is the limiting factor at these frequencies.
  • Star arrangement at the panel, not daisy chain. Every earthed item returns to the bar by its own path; nothing gets its earth through another device's terminal.

Filters, reactors and when they are needed

Where the motor cable run exceeds the drive manufacturer's limit — commonly 30 to 50 m shielded, less unshielded — an output reactor or a dv/dt filter protects the motor insulation and reduces the common-mode current. Where the supply is weak or has a high fault level with capacitor banks, a line reactor or DC choke reduces harmonic current and protects the drive's input rectifier.

EMC filter for the installation is a separate question: it addresses emissions conducted back into the supply. Most drives have a built-in filter adequate for the second environment (industrial). First environment — residential or light commercial — needs an external filter and a documented earth arrangement.

Symptoms and their usual cause

SymptomFirst thing to check
Analogue readings drift when a drive runsScreen pigtailed, or analogue cable parallel to motor cable
Encoder counts jumpEncoder cable screen not bonded at the drive end
PLC faults randomlyEarth bar arrangement, common-mode path through control panel
Motor bearing failure at low hoursShaft current — check earthing and consider a bearing current kit
Radio or network interference nearbyMotor cable unshielded, or screen not bonded

On the VFD control cabinets we build, screened motor cables land on a dedicated EMC bar directly below the gland plate, and the bar is bonded to the enclosure at both ends with braid. It costs a few minutes per panel and it is the reason our drive panels do not come back with noise complaints.