Sizing a Brake Resistor for a Hoist or Conveyor
Braking is energy, and energy is a number. Hoists, cranes, downhill conveyors and any load that overhauls the motor feed power back into the drive's DC bus. If nothing absorbs it, the bus voltage climbs until the drive trips on overvoltage — usually at the worst moment in the cycle.
Work out the joules first
Take the load's potential energy released per stop: mass × gravity × drop height. Add the kinetic energy of moving parts. Divide by the stopping time to get the braking power in watts, then look at the duty cycle: a hoist that brakes twice a minute needs a very different resistor from one that brakes twice an hour. Resistors are rated on average power and peak power separately, and quoting only one of the two is how a resistor ends up glowing.
Matching the resistor to the drive
Minimum resistance is set by the drive's braking transistor and is in its manual. Going below it pulls too much current through the chopper; going far above it reduces braking torque. The enclosure also matters: a resistor dissipates heat into the panel or into the room, and in a sealed cabinet that heat comes back as a temperature rise. Many builds mount the resistor outside the enclosure with a thermal switch wired back to the drive.
For hoists, the safe design assumes the brake is mechanical and the resistor is an assist, not the primary stopping method. The VFD control cabinet is normally supplied with a brake chopper, an external resistor prepared for wall mounting, and a thermostat in series with the drive's fault input. The group drive note explains why dynamic braking becomes difficult when several motors share one drive.