Cooling a Sealed Panel: Fans, Heat Exchangers or Air Conditioners

Column: Technical Notes    Time: 2026-04-28

Sealed enclosure, drives inside, ambient above 40 °C. The heat has to leave somehow, and there are three ways to make it leave: move air through a filter, move heat through a plate, or run a refrigeration circuit. Each has a different maintenance load, and the choice follows from the site rather than from the catalogue.

Start with the watts

Before selecting anything, add up the losses. Nameplate data is the starting point, not the answer:

  • Drive losses: roughly 3 to 5 per cent of motor kW at full load for a standard drive, lower for a high-efficiency unit. A 30 kW drive at 4 per cent is 1.2 kW of heat inside the cabinet.
  • Transformers: 2 to 4 per cent of rating, and they run continuously.
  • Power supplies, relays, contactors, meters: small individually, 100 to 300 W for a typical control section.
  • Solar gain through a sunlit wall: can exceed the internal losses on a west-facing outdoor cabinet.

Panel internal temperature is ambient plus the rise from those watts. Target is usually 40 °C internal for drives and 45 °C for control gear; check the components rather than assuming.

The three options

MethodTypical capacityBest forWatch out for
Filter fan and outlet filter100 – 1000 WClean indoor air, dust not conductivePulls dust in; filter maintenance
Air-to-air heat exchanger300 – 3000 WDusty or oily air; sealed enclosureOnly works if outside air is cooler
Panel air conditioner500 – 5000 WHigh ambient, sealed, washdown areasCondensate drain, power draw, service
Heat pipe / thermosiphon200 – 1500 WSealed, no power available at the panelNeeds vertical mounting

Filter fans are cheap and need attention

Filter fan moves ambient air through the enclosure and out through an outlet filter. It is the lowest-cost option by a wide margin and works well in a clean plant room. It fails in three predictable ways:

  • Dust. Filter mats load up and airflow falls. On a foundry or a woodworking site the mat can clog in weeks, and nobody notices until a drive trips on over-temperature.
  • Conductive dust. Carbon or metal dust passing a filter is worse than the heat it was removing.
  • Pressure imbalance. Filter fan plus outlet filter of the wrong size drives the enclosure positive or negative, pulling air through every gland and door seal rather than through the filter.

Where a filter fan is the right answer, we specify a differential pressure switch or at least a maintenance label with the mat part number, so the next person can order the right one.

Heat exchangers when the air is dirty

Air-to-air exchanger keeps the enclosure sealed and transfers heat through a plate or a heat pipe core. No dust enters, no filter to change on the inside. Its limit is physics: it can only reject heat if the outside air is cooler than the inside air, and capacity falls steeply as the two approach each other.

On a site where summer ambient is 38 °C and the target internal temperature is 40 °C, an exchanger has almost no driving temperature difference and will disappoint. That is the case for air conditioning, not a bigger exchanger.

Air conditioners and their hidden requirements

Panel air conditioner is a refrigeration circuit mounted on the door or side wall. It holds internal temperature regardless of ambient and keeps the enclosure sealed, which suits washdown and dusty sites.

Three requirements that get forgotten:

  • Condensate. Needs a drain, or an evaporator that re-boils it. On an outdoor cabinet, a blocked drain in winter is a frozen drain.
  • Power and protection. A 1 kW cooling unit draws several hundred watts and needs its own supply and protection inside the panel, which adds to the heat load it is fighting.
  • Service access. Filters on the condenser side need cleaning. Mounting the unit where a technician cannot reach it without a ladder is a maintenance problem waiting to happen.

What we ask before sizing

  • Total internal losses, or the drive list so we can calculate them.
  • Maximum ambient and how many hours a year it is exceeded.
  • Whether the air is dusty, oily, corrosive or washdown.
  • Indoor or outdoor, sun exposure, and the mounting orientation.
  • Whether the enclosure must stay sealed for process reasons.

Those five answers reduce the choice to one or two options. On the fan and HVAC control cabinets we build for plant rooms, most panels end up with a filter fan and a thermostat; outdoor units on roofs almost always go to an air conditioner with a drip shield.