Replacing Obsolete Drives on a Paper Machine
Paper machine drive from 1998, no spare parts available, and a machine that runs continuously. The decision was retrofitted rather than run to failure, and the retrofit had to happen in planned shutdown windows.
The risk
Running to failure means an unplanned stop of a machine that produces several hundred tonnes a day, with no replacement drive available on the market. The retrofit risk is that the new drive does not reproduce the old one's torque behaviour, and the paper breaks on every speed change.
Approach
The old drive's parameters were recorded before removal, the load profile measured with a data logger over two weeks, and the new drive commissioned on a test stand with a dynamometer before it went near the machine. Section by section, one shutdown at a time.
Result
Two sections needed retuning after the first production run, both within the shutdown window. The old drive was kept as a spare for the remaining sections until all were replaced. Retrofits like this succeed on measurement, not on datasheets. The retrofit note covers the survey method, and the VFD control cabinet for this project was built with the old drive's interface signals replicated.