Heat Inside a Sealed Cabinet: Four Numbers That Decide the Enclosure
Sealed enclosures are sold as the safe answer for dusty, humid or washdown plants. They are, provided the heat has somewhere to go. Four numbers decide that, and only one of them is usually in the enquiry.
Ambient temperature, measured where the panel stands
Design ambient is not the same as the weather forecast. Cabinets against a west-facing wall in a steel-framed shed run ten degrees above the shade reading for two hours every afternoon. Ask for the summer maximum at the panel face, not at the site gate. Where the figure is genuinely unknown, assume forty-five degrees and let the supplier design against it.
Dissipated watts, not motor kilowatts
Drive losses run around three percent of motor rating at full load, and a 75 kW motor therefore puts roughly two kilowatts of heat inside the box. Add transformer losses, power supply losses, relay coils and indicator lamps. The total is the number the enclosure design works from, and it is rarely supplied with the drawing package.
Effective surface area
Heat leaves through the steel, so the geometry matters. Bolting a cabinet flat against a wall loses one face; a row of cabinets fixed together loses the shared sides as well. Both are normal installations, and both halve the effective area if nobody corrects for it. This is where a sealed enclosure reaches its limit and a heat exchanger becomes cheaper than a larger box.
Duty cycle and load profile
Continuous full-load duty is the worst case, but most fans and pumps run at part load most of the year. The temperature rise that matters is the one reached on the hottest afternoon at the highest production rate, so design for the peak and check the steady state afterwards.
The fan and HVAC control cabinet is the clearest example: the fan motor itself adds heat, the filter adds resistance, and the enclosure has to hold both without the internal temperature climbing past the rating of the drive. Where the plant rules out filtered air, we build the same panel with a sealed exchanger and no fan opening at all. Sizing notes for the wider range are on the fan control cabinets page.
Send those four numbers with the enquiry and the enclosure size stops being a guess. Send only the motor rating and the quotation is a guess that looks like a calculation.